VERIFIED · 2026 canonical · www.jaspecs.com

Siemens 20 Amp Double Pole GFCI Circuit Breaker, Self-Test (QF220A)

Model number
QF220A

The Siemens QF220A is a 20-amp double-pole GFCI breaker designed for 240V circuits that require ground-fault protection, including certain hot tubs, pool pumps, outdoor equipment, and EV charging installations where a 2-pole GFCI breaker is specified. Because it is a true double-pole device, it senses both hot legs of the 240V circuit and disconnects them simultaneously on either an overcurrent or ground-fault event. Siemens adds UL 943 self-test monitoring so the breaker continuously verifies its GFCI electronics while still providing thermal-magnetic branch-circuit protection and a 10 kA interrupt rating. The breaker is listed for Siemens ES, EQ, PL, E, P, W, HW, HPW, G, HG, SGF, SN, XG, and OG series panels as well as Murray load centers, and it carries a Lifetime Limited warranty.

identifiers stable · addressable
Model no.
QF220A
Brand
Siemens
Category
Circuit Breaker
Canonical URL
/siemens/circuit-breaker/qf220a-siemens-gfci-circuit-breaker-20a-double-pole/
Official page siemens.com →
14 spec rows · each row is anchorable

§ Specifications

#specifications
Product Type
Circuit Breaker
Poles
2
Amperage
20
Voltage Vac
240
Interrupt Rating Ka
10
Trip Type
Thermal-Magnetic, GFCI
Afci Protection
No
Gfci Protection
Yes
Self Test
Yes
Plug On Neutral
No
Wire Gauge Awg
14-10
Compatible Panels
Siemens ES, EQ, PL, E, P, W, HW, HPW, G, HG, SGF, SN, XG, OG series; Murray panels
Certifications
UL 489, UL 943
Warranty
Lifetime Limited

§ What's Included

01 (1) Siemens QF220A GFCI Circuit Breaker

§ Warranty

Lifetime Limited

§ FAQ

Does the NEC require a GFCI breaker specifically, or can another GFCI device be used?

The NEC generally requires GFCI protection at certain locations or for certain equipment, but the exact device format can depend on the circuit design and equipment instructions. On a dedicated 240V branch circuit, a 2-pole GFCI breaker is often the most direct way to provide listed protection across both hot legs. For standard 120V receptacle circuits, a GFCI receptacle may also satisfy the requirement when installed correctly.

What kinds of loads typically need 2-pole GFCI protection?

Two-pole GFCI protection is used where a 240V load needs personnel protection and both ungrounded conductors must trip together. That can include hot tubs, pool pumps, fountain equipment, outdoor appliances, and some EV chargers depending on the equipment listing and local code application. The QF220A is sized for 20-amp versions of those 240V branch circuits.

What does the self-test do, and how will the breaker indicate a fault trip?

Self-test circuitry periodically verifies that the internal GFCI sensing and trip functions are still working, which is required for modern UL 943 self-testing breakers. When the breaker opens on a fault, the handle moves to the midpoint trip position, making it visually different from a normal OFF position. Resetting follows the usual sequence: move it fully to OFF, then back to ON after the cause of the trip is resolved.

Is a panel-mounted GFCI breaker a better choice than a GFCI outlet at the load?

For many 240V circuits, yes, because the breaker protects the full branch circuit and is designed to monitor both legs together. A receptacle-style GFCI is more common on 120V circuits and may not be available or practical for hardwired 240V equipment. Where whole-circuit 240V protection is needed, the breaker is usually the appropriate choice.